EZ-ZONE® High-Density Control Module (RMH)

EZ-ZONE® High-Density Control Module (RMH)


High-Density Control Module Specifications (RMH)

(Select an RMH module for 4 to 16 loops of control.)

Requires 24 to 28VAC/VDC power supply, includes communication port for configuration with EZ-ZONE configurator and PC.

    Line Voltage/Power

  • Power consumption: 7 W, 14VA
  • Any external power supply used should comply with a Class 2 or SELV rating Controller
  • User-selectable heat/cool, on-off, P, PI, PD, PID or alarm action, not valid for limit controllers
  • Process PID Options

  • Auto-tune with TRU-TUNE+ adaptive control
  • Control sampling rates: input = 10Hz, output = 10Hz (non-divisional)
  • Isolated Serial Communications

  • All modules ship with standard bus protocol for configuration and communication with all other EZ-ZONE controllers
  • Optional EIA 485, Modbus® RTU
  • Calibration Accuracy

  • ±0.1% of span, ±1°C. See user manual for details.
  • Universal Input

  • Thermocouple, grounded or ungrounded sensors
  • >20MΩ input impedance
  • Max. of 2kΩ source resistance
  • RTD 2-wire, platinum, 100Ω and 1000Ω @ 32°F (0°C) calibration to DIN curve (0.00385Ω/Ω/°C)
  • Process, 0-20mA @100Ω, or 0-10VDC @ 20kΩ input impedance; scalable, 0-50mV
  • Thermistor Input

  • 0 to 40kΩ, 0 to 20kΩ, 0 to 10kΩ, 0 to 5kΩ
  • 2.252kΩ and 10kΩ base at 77°F (25°C)

Digital Input

  • Update rate 10Hz
  • Max. input 36VDC at 3mA
  • Min. high state 3VDC at 0.25mA
  • Dry Contact Input

  • Update rate 10Hz
  • Min. open resistance 10kΩ, max. closed resistance 50Ω
  • Output Hardware

  • 6 digital inputs/outputs:
  • Switched dc, max. 20VDC @ 40mA, 12VDC @ 80mA
  • Open collector, max. 32VDC @ 1.5A, max. 8A per 6 outputs combined
  • Electromechanical relay, Form A, 5A, 24 to 240VAC or 30VDC max., resistive load, 100,000 cycles at rated load, requires a min. load of 20mA at 24V, 125VA pilot duty
  • Tri-Process (Three universal process/retransmit outputs)

  • Output range selections: 0 to 10VDC into a min. 4KΩ load
  • 0 to 20mA into max. 400Ω load
  • Quad SSR

  • Four SSRs at 2A each. SSRs are grouped in 2-pairs with each sharing a common. See table.
  • Maximum Current Per Relay

    Ambient Temp. 1 Quad SSR Card More than 1 Quad SSR Card
    -18 to 20°C 2A 1.5A
    20 to 65°C 1A 0.75A


    (4) Connector Style
    A = Right angle screw connector (standard)
    F = Front screw connector
    S = Custom

     

    (5) Slot A
    1 = 4 universal inputs (T/C, RTD 2-wire, 0-10VDC, 0-20mA) with control loops
    2 = 4 thermistor inputs with control loops

     

    (6) Slot B
    A = None
    1 = 4 universal inputs (T/C, RTD 2-wire, 0-10VDC, 0-20mA) with control loops
    2 = 4 thermistor inputs with control loops

     

    (7) Slot D
    A = None
    1 = 4 universal inputs (T/C, RTD 2-wire, 0-10VDC, 0-20mA) with control loops
    2 = 4 thermistor inputs with control loops
    C = 6 digital I/O
    F = 3 universal process/retransmit outputs
    J = 4 mechanical relay 5A, Form A
    L = 4 SSR’s at 2A each. SSR’s grouped in 2-pairs with each pair sharing a common.

     

    (7) Slot E
    A = None
    1 = 4 universal inputs (T/C, RTD 2-wire, 0-10VDC, 0-20mA) with control loops
    2 = 4 thermistor inputs with control loops
    C = 6 digital I/O
    F = 3 universal process/retransmit outputs
    J = 4 mechanical relay 5A, Form A
    L = 4 SSR’s at 2A each. SSR’s grouped in 2-pairs with each pair sharing a common

     

    (10) Enhanced Options
    A = Standard Bus
    1 = Standard Bus and Modbus® RTU 485 (user-selectable)

     

    (11)(12) Additional Options
    AA = Standard
    AB = Replacement connectors hardware only for the entered model number
    XX = Custom